Standard
High Duty
Recessed
Cold Store
Industrial
Architectural

Controls
and Wiring

Standard Models

standardmodelThis elegant slimline range of powerful modular air curtains, built to a high quality are suitable for pedestrian doorways up to a height of 2.7 metres and a width of 2 metres. They are used in shops, offices, retail outlets, manufacturing facilities, reception areas and warehouses. These units are available with hot water coils or electric heaters and finished in a high quality epoxy polyester powder RAL 9010. (Other colours are available on request).

This range meets with the specifiers and end users needs - low cost, continuously rated, easy to install and service.


Model Heat
output
Max
current
Motor
power
Voltage Max air
vol m3/h
Max height Noise level
d(B)A
Weight
kg
ACD 10A   0.52A 60W 220V/1 ph 1490 2.7m 55/52 20
ACD 10W 8kW 0.52A 60W 220V/1 ph 1300 2.7m 54/51 24
ACD 10E 7kW 10A* 60W 380V/3 ph 1400 2.7m 55/52 23
ACD 15A   0.52A 60W 220V/1 ph 2200 2.7m 56/53 30
ACD 15W 12kW 0.52A 60W 220V/1 ph 2000 2.7m 55/52 36
ACD 15E 12kW 17A* 60W 380V/3 ph 2100 2.7m 56/53 35
ACD 20A   1.04A 120W 220V/1 ph 2980 2.7m 58/55 40
ACD 20W 16kW 1.04A 120W 220V/1 ph 2600 2.7m 57/54 48
ACD 20E 14kW 20A* 120W 380V/3 ph 2800 2.7m 58/55 46

* per ph

Suitable for 230/400V supply.
LTHW at 80/60 Deg C

Dimensions   Fixing Details
  Unit Dimensions
Model A
mm
B
mm
C
mm
ACD 10A 1100 300 200
ACD 10W 1100 300 200
ACD 10E 1100 300 200
ACD 15A 1600 300 200
ACD 15W 1600 300 200
ACD 15E 1600 300 200
ACD 20A 2200 300 200
ACD 20W 2200 300 200
ACD 20E 2200 300 200
 
  Unit Fixing Positions
Model D
mm
E
mm
F
mm
ACD 10A 1040 190 1040
ACD 10W 1040 190 1040
ACD 10E 1040 190 1040
ACD 15A 1540 190 1540
ACD 15W 1540 190 1540
ACD 15E 1540 190 1540
ACD 20A 2140 190 2140
ACD 20W 2140 190 2140
ACD 20E 2140 190 2140

For ACD 2 metre fixing details use ACD 10 x 2

ACD Technical Water Table

ACD 10W
 
Water temperature (deg C)
80/60 82/71 90/70 110/90
Heat output (kW)
8 8.66 8.5 10.1
Water pressure drop (kPa)
2 7.5 2.5 3.3
Water flow rate (I/s)
0.09 0.19 0.1 0.13
EAT (deg C)
16 16 16 16
LAT (deg C)
34.1 37.2 36.8 41
Air volume (m3/s)
0.36 0.36 0.36 0.36

ACD 15W
 
Water temperature (deg C)
80/60 82/71 90/70 110/90
Heat output (kW)
12 12.3 12.2 14.4
Water pressure drop (kPa)
5.4 18.5 6.2 8
Water flow rate (I/s)
0.14 0.28 0.15 0.18
EAT (deg C)
16 16 16 16
LAT (deg C)
33.9 35.6 35.5 39.1
Air volume (m3/s)
0.55 0.55 0.55 0.55

ACD 20W
 
Water temperature (deg C)
80/60 82/71 90/70 110/90
Heat output (kW)
16 17.32 17 20.2
Water pressure drop (kPa)
2 7.5 2.5 3.3
Water flow rate (I/s)
0.18 0.38 0.2 0.26
EAT (deg C)
16 16 16 16
LAT (deg C)
34.1 37.2 36.8 41
Air volume (m3/s)
0.72 0.72 0.72 0.72

NOTE: All water connections are 3/4" BSP


High Duty Fixing Diagram